potentialpaper

Certified Single-Level Reformulation for Tri-Level Cyber-Physical Grid Security

Debraj Banerjee, Gurunath Gurrala, Kunal N. Chaudhury

NeurIPS 2026

Edit this page

Or clone it with git

Run in a terminal:

Needs Git LFS. To push, use an API key from your profile as the password.

Or let your agent set it up

It checks and sets up everything: signing in, git, the clone, credentials and an SSH key.

TL;DR. SL-MILP/MICP: certified single-level DC/AC optimal power flow reformulations of the tri-level cyber-physical grid security problem, enabling tractable defense optimization with provable worst-case robustness guarantees.

Abstract. Modern power grids are increasingly exposed to coordinated cyber-physical disruptions, where the outage of a small number of transmission components can trigger severe post-contingency load shedding. Designing proactive security defense against such adversarial contingencies is naturally modeled as a tri-level Defender-Attacker-Operator (DAO) problem: the defender allocates limited hardening resources, the attacker selects worst-case line outages, and the operator solves a post-attack DC/AC-optimal power flow (OPF). However, the resulting tri-level program is computationally prohibitive even for moderate network sizes.

We develop a certified four-step reformulation pipeline that converts this intractable tri-level DAO problem into a tractable single-level optimization, yielding a Single-Level Mixed-Integer Linear Program (SL-MILP) under DC-OPF and a Single-Level Mixed-Integer Conic Program (SL-MICP) under a convex SOCP relaxation of AC-OPF. The construction is exact except for one controlled relaxation of the attacker's binary decisions. It provides two complementary guarantees: the single-level value SSLS_{\mathrm{SL}} is an a-priori conservative bound, while one post-hoc binary attacker-operator solve at the returned defense gives the exact realized certificate Strue(dSL∗)≤SSLS_{\mathrm{true}}(d^*_{\mathrm{SL}})\le S_{\mathrm{SL}}. Experiments on IEEE power systems up to 118 buses for DC and 57 buses for AC quantify both certificate gaps and runtime while demonstrating substantial computational gains.

Are you an author? Claim this paper to see who's reading it, with views and other statistics, and to write about it here.

Claim this paper
How does this paper connect to your work? Write how you built on it, compared with it or reproduced it, or add a summary, a critique or errata.
Or make it interactive:
Start writing

edit · history

DateVersionSubmitted toPDFEvidence
4 May 2026NeurIPS 2026submittedNeurIPS 2026Accept (poster)reviews ↓[1]PDF[1]
Missing a version?

NeurIPS 2026

Accept (poster) · 3 reviews · OpenReview

Updated 25 Nov 2026, 03:46 UTC.

Program Chairs · DecisionOpenReview ↗
Decision
Accept (poster)
Read decision
Meta-review

This paper develops certified single-level reformulations of a tri-level grid-defense problem for DC and SOCP-relaxed AC models. The rebuttal largely addresses the concerns about notation, Big-M bounds, certificate gaps, and experimental scope. It also appropriately clarifies that the AC certificate applies only to the SOCP model, not the nonconvex AC-OPF. Although AC validation and large-scale evaluation remain limited, these are limitations rather than fundamental flaws. I recommend acceptance.

Final justification

The rebuttal resolves the main technical concerns and appropriately narrows the AC guarantee. The remaining limitations do not undermine the core DC and SOCP contributions.

Area Chair r4sy · Meta-reviewOpenReview ↗
Read meta-review
Meta-review

This paper develops certified single-level reformulations of a tri-level grid-defense problem for DC and SOCP-relaxed AC models. The rebuttal largely addresses the concerns about notation, Big-M bounds, certificate gaps, and experimental scope. It also appropriately clarifies that the AC certificate applies only to the SOCP model, not the nonconvex AC-OPF. Although AC validation and large-scale evaluation remain limited, these are limitations rather than fundamental flaws. I recommend acceptance.

Final justification

The rebuttal resolves the main technical concerns and appropriately narrows the AC guarantee. The remaining limitations do not undermine the core DC and SOCP contributions.

1 comment
Authors · CommentOpenReview ↗

Response to the Meta Review

We thank the Area Chair for the constructive meta-review. We address the major concerns below and clarify the scope of our theoretical guarantees.

  • The certification guarantee is clarified precisely.
    The only approximation in the DC pipeline is the attacker relaxation, which can only enlarge the attack set and therefore yields a conservative certificate. The selected defense is then certified exactly via the merged defender-operator problem. (See our response to Reviewer L6eE: W2, W6, Q and Reviewer Qe5o: Q(ii), Q(v))

  • All Big-M constants are derived analytically.
    We derive closed-form bounds from physical limits and dual feasibility, prove boundedness (Lemma R1), provide an explicit construction algorithm, and add an a-posteriori envelope-activity check. No heuristic tuning is required. (See our response to Reviewer L6eE: W3, Reviewer 3m6F: W2, Q2, and Reviewer Qe5o: Q(iv).)

  • The certificate gap is now quantified.
    We report the exact merged-problem value Strue(dSL∗)S_{\mathrm true}(d_{SL}^* ), the certificate gap ΔC\Delta_C, and the gap to the original tri-level optimum Δ0\Delta_0 for every benchmark, directly validating Theorem 5.4. (See our response to Reviewer L6eE: W6, Q and Reviewer 3m6F: Q3)

  • The SOCP-versus-AC gap is evaluated explicitly.
    We compare the SOCP relaxation with the exact AC-OPF on the IEEE 9-bus system. Both attain the same optimal objective with zero load shedding. Active-power dispatch, voltage magnitudes, and phase angles are nearly identical. (See our response to Reviewer 3m6F: W3)

  • The experimental scope is clarified.
    The DC formulation is evaluated on seven IEEE systems (5, 9, 14, 22, 30, 57, and 69 buses). For the AC formulation, we also include AC results for the IEEE 14-, 30-, and 57-bus systems. (See our response to Reviewer L6eE: W5 and Reviewer Qe5o: Q(i).(c))

  • Notation has been unified.
    We will correct all typographical inconsistencies, unify the notation, and add complete variable lists and a glossary. These changes are editorial only; the derivations, implementation, and results are unchanged. (See our response to Reviewer L6eE: W1 and Reviewer 3m6F: W1)

Overall, we believe the rebuttal resolves the technical concerns raised in the reviews and the meta-review. The certification guarantee is now stated precisely, the Big-M construction is fully justified, the conservative gaps are quantified, and the AC relaxation is evaluated empirically.

Reviewer Qe5oOpenReview ↗
Rating
4/6
Confidence
4/5
Quality
3/4
Clarity
3/4
Significance
2/4
Originality
2/4
Contribution type
use_inspired
Ethical concerns
NO or VERY MINOR ethics concerns only
Read review
Summary

The paper studies a tri-level defender-attacker-operator (DAO) grid-security game: a defender hardens lines, an attacker interdicts lines, and an operator minimizes load shed via OPF. The authors reformulate this min-max-min problem into a single-level problem by repeatedly dualizing inner levels and using Big-M to linearize bilinear terms. The DC case yields a single-level MILP; the AC case uses an SOCP relaxation and yields a single-level MICP. Theorems (Thm 5.1/5.2/5.4) claim the single-level optimum S_SL is a conservative upper bound on the true tri-level worst-case load shed, with a safety certificate for the deployed defense. Table 3 on IEEE 14-bus DC validates the upper-bound property against exact enumeration and reports fast solve times (about 7–46 ms). An AC variant is shown on WSCC 9-bus.

Strengths and weaknesses

Strengths. This is the most mathematically structured paper in its line: the dualization + Big-M pipeline has explicit exactness theorems at each step. The DC part is genuinely validated — Table 3 confirms S_SL is a valid upper bound vs exact enumeration, and scalability figures show large speedups over enumeration/Benders-style baselines. The writing is clear and future work is candid about SOCP gaps.

Weaknesses. The headline claim — first certified single-level reformulation with AC in a tri-level game — is largely unvalidated. DC runs on 14-bus; AC runs on 9-bus, so even informal comparison is impossible. Table 4 reports SOCP relaxation values, not true AC OPF; the SOCP-true-AC gap is never measured. Table 4 also has no baseline, no runtime, and no DC-vs-AC comparison on the same system — yet "AC is worth it" and "fast single solve" are central motivations. Without (i) evaluating DC-derived and AC-derived defenses under one common true-AC power flow (e.g., MATPOWER), (ii) measuring SOCP vs true AC gap, and (iii) AC runtime at 14/30/57 buses, removing the unvalidated AC part leaves mainly a faster known DC upper bound.

The safety certificate is proved inside the SOCP model, not on true nonconvex AC. Relaxing the attacker upward helps conservatism, but SOCP can underestimate damage for a fixed attack — so S_SL >= true-AC worst case is not automatic. This matters most where the paper argues AC is needed (high-stress post-attack conditions), where SOCP is often loosest.

Other gaps: Big-M values are not specified or justified, yet exactness and the "7–50 ms" speed claim depend on M; Table 4 generation cost is non-monotonic in D (2947.96 -> ... -> 8991.25 at D=3 -> 6505.94) with no explanation; Table 3 conservatism can reach about 2x (A=2, D=2: true 6.1 vs bound 12.5) despite calling the gap "small."

Questions

(i) Your main novelty is embedding AC in the tri-level game, but DC is on 14-bus and AC on 9-bus — no apples-to-apples comparison. Table 4 is SOCP, not true AC, and has no baseline or runtime. Please: (a) evaluate defenses from DC and AC reformulations under the same true-AC power flow (MATPOWER); (b) report SOCP vs true-AC gap; (c) run AC to 14/30/57 buses with runtime. This directly tests whether AC is worth the added complexity.

(ii) Please clarify conditions under which each dualization step is exact. What happens when inner problems are nonconvex (true AC-OPF)? Which guarantees (upper bound, certificate) hold only under SOCP/convex inner models vs true AC? A explicit statement of what is proved for nonconvex inner OPF would clarify scope.

(iii) Table 4, As D increases, generation cost goes 2947.96 -> 3252.21 -> 3533.50 -> 8991.25 -> 6697.50 -> 6505.94, with a sharp jump at D=3. Since the objective combines load shed and quadratic generation cost, please explain this behavior (different SOCP operating points, Big-M/numerical effects, or suboptimal MICP solve).

(iv) What value of Big-M. is used, how is it derived from variable/dual bounds, and how sensitive are bound quality and solve time to M? Without this, exactness of the bilinear linearization and the reported speed are hard to assess, especially in the AC/SOCP setting.

(v) On 9-bus, does S_SL upper-bound worst-case load shed under true nonconvex AC-OPF for all binary attacks on d_SL? If not, please scope "certified" to "within the SOCP model."

Limitations

Limitations should front-load that AC results are SOCP-only on 9-bus with no DC comparison; the certificate may not transfer to true AC; conservatism can be large (Table 3); and Big-M choices are undocumented. Future work mentions some of this but it should be in the main limitations with deployment scope.

Final justification

Thank you for the clarifications. The concerns regarding the Big-(M) construction, certificate-gap reporting, DC certification, experimental scope, and notation have been largely addressed.

One major issue remains. The comparison on the IEEE 9-bus system does not establish that the SOCP-based certificate is valid for the original nonconvex AC model, especially under stressed post-attack conditions. Please clarify whether “exact AC-OPF” is globally solved and, unless stronger evidence is provided, state explicitly that the AC certificate applies only to the SOCP-relaxed model.

Finally, future responses should reproduce all substantive answers directly. Reviewers are not obligated to search across separate response threads referenced only by labels.

Formatting concerns

no

3 comments
Authors · RebuttalOpenReview ↗
Rebuttal

Q(i)

(a) Please check our response to Q3 of Reviewer 3m6F, where we have discussed this.

(b) We have evaluated the gaps (see our response to W3 of Reviewer 3m6F)

(c) Similar to Table 4 and our response in Q3 of Reviewer 3m6F, we run tri-level AC-OPF benchmarking (with only load shed as objective) on IEEE 14, 30 and 57 bus systems with A=2A=2 and D=0,1,2,3D=0, 1, 2, 3 to obtain the following results:

IEEE 14-bus:

DD protected lines $d_{SL}^* $ SSLS_{SL} (MW) Strue(dSL∗)S_{true} (d_{SL}^* ) (MW) ΔC\Delta_C (MW) S∗S^* (MW) Δ0\Delta_0 (MW) worst-case attack runtime (s)
0 (none) 14.9 14.9 0.0 14.9 0.0 9–14, 13–14 0.50
1 9–14 12.5 12.5 0.0 12.5 0.0 6–11, 9–10 0.53
2 9–10, 9–14 12.5 9.0 3.5 6.1 2.9 6–12, 12–13 0.77
3 6–12, 9–10, 9–14 6.2 6.1 0.1 3.5 2.6 6–11, 10–11 0.91

IEEE 30-bus:

DD protected lines $d_{SL}^* $ SSLS_{SL} (MW) Strue(dSL∗)S_{true} (d_{SL}^* ) (MW) ΔC\Delta_C (MW) S∗S^* (MW) Δ0\Delta_0 (MW) worst-case attack runtime (s)
0 (none) 30.0 30.0 0.0 30.0 0.0 6–8, 8–28 2.63
1 6–8 24.0 22.8 1.2 21.8 1.0 2–5, 6–7 2.98
2 6–7, 6–8 19.5 17.5 2.0 17.3 0.2 10–21, 21–22 3.01
3 6–7, 6–8, 10–21 16.5 14.9 1.6 12.8 2.1 15–18, 10–20 3.83

IEEE 57-bus:

DD protected lines $d_{SL}^* $ SSLS_{SL} (MW) Strue(dSL∗)S_{true} (d_{SL}^* ) (MW) ΔC\Delta_C (MW) S∗S^* (MW) Δ0\Delta_0 (MW) worst-case attack runtime (s)
0 (none) 43.0 43.0 0.0 43.0 0.0 1–16, 12–16 10.07
1 1–16 42.5 42.0 0.5 41.3 0.7 1–17, 12–17 11.06
2 1–16, 1–17 40.5 39.0 1.5 37.1 1.9 49–50, 10–51 11.70
3 1–16, 1–17, 49–50 37.5 35.8 1.7 32.8 3.0 29–52, 9–55 12.55

In every case, our SL-MICP formulation gives results close to the true values and the certifiicate $d_{SL}^* $ remains reliable.


Q(ii)

To state the scope explicitly: every dualization step is exact only for convex inner models (Lemmas 2.1/4.1 (LP) and 2.2/4.3 (SOCP) supply the strong duality used in Theorem 5.1), and no guarantee is claimed for a nonconvex inner AC-OPF. What is proved: (upper bound + certificate) hold unconditionally for DC; and for AC they hold with respect to the relaxed SOCP operator model.

In practice, the SOCP relaxation is tight on our benchmark (see our response to W3 of Reviewer 3m6F), where the exact AC-OPF and SOCP attain the same objective with nearly identical dispatch and voltage profiles. We will add an explicit statement after Theorem 5.4 to clarify the scope of the guarantees.


Q(iii)

The non-monotonicity is model behavior, not a numerical artifact. The defender minimizes the worst-case mixed objective (shed + cost) (lines 106 to 111), so generation cost need not be monotone in DD for three compounding reasons visible in Table 4 itself: (1) the worst-case attack changes with DD (column 3: the attacked pair is different in every row), so consecutive rows evaluate cost on different surviving network topologies; (2) because shedding dominates the weighted objective, the defender deliberately buys shedding reductions with expensive dispatch: at D=3D = 3 shedding drops 97.3→66.197.3 \to 66.1 MW precisely by pushing the surviving network to costly operating points on the quadratic cost (eq. (5e)), producing the jump to 8991.258991.25; (3) at D=4,5D = 4, 5 the additional protected lines (11--44, then 88--22, 99--44) restore cheaper delivery paths, so cost falls again while shedding continues to 00.

Also generation cost only depends on power generation, and we do not assume any defence cost (hence increase in number of defence should not be assumed to directly increase generation cost).


Q(iv)

We have discussed this extensively in our response to W3 of Reviewer L6eE: for DC, we can set Mλ=Mϕ=1M_\lambda = M_\phi = 1, which is valid by Lemma R1: unit shedding penalty and the shedding slacks guarantee feasibility for every topology by Lemma 2.1. My=max⁡i,j(θimax⁡−θjmin⁡)M_y = \max_{i,j} (\theta_i^{\max} - \theta_j^{\min} ) from the constraints in eq. (2a)/(39); for AC, Mx=max⁡(∣xmin⁡∣,∣xmax⁡∣)M_x = \max(|x^{\min} |, |x^{\max} |) componentwise from the constraints in eq. (5a)/(17). On sensitivity: for any MM at or above these valid thresholds, the linearization is exact (Definition A.4), so the bound value is MM-independent in the valid regime; solve-time sensitivity and the envelope-activity check will be reported per system in the revision. The reported 7--50 ms runtimes were obtained with the constants above, not with loose ad-hoc values.


Q(v)

As we have discussed in Q(ii), we do not theoretically claim that SSLS_{SL} automatically upper-bounds the true nonconvex-AC worst case; "certified" will be scoped to "within the SOCP model".

As our SOCP relaxation is tight (see our response to W3 of Reviewer 3m6F), we empirically get better results where SSLS_{SL} (shedding due to the relaxed attacker under defense $d_{SL}^* $) always gives an upper bound to the true optimal shedding S∗S^* (as observed in Table 3, Figure 2 from the mnuscript and the results shown in response to Q3 of Reviewer 3m6F and response to Q(i).(c) above)

Reviewer Qe5o · CommentOpenReview ↗

Thank you for the clarifications. The concerns regarding the Big-(M) construction, certificate-gap reporting, DC certification, experimental scope, and notation have been largely addressed.

One major issue remains. The comparison on the IEEE 9-bus system does not establish that the SOCP-based certificate is valid for the original nonconvex AC model, especially under stressed post-attack conditions. Please clarify whether “exact AC-OPF” is globally solved and, unless stronger evidence is provided, state explicitly that the AC certificate applies only to the SOCP-relaxed model.

Finally, future responses should reproduce all substantive answers directly. Reviewers are not obligated to search across separate response threads referenced only by labels.

Authors · CommentOpenReview ↗

We are glad to know that the concerns regarding the Big-MM construction, certificate-gap reporting, DC certification, experimental scope, and notation have been resolved.

We agree that our current theory does not establish the certificate for the original nonconvex AC-OPF under all operating conditions. And we confirm that we do NOT solve the nonlinear AC-OPF globally, hence we do not claim a theoretical certificate for the nonconvex AC model.

The proven upper-bound and certification guarantees apply to the SOCP-relaxed AC operator model, where every dualization step is exact by strong duality. We will revise the manuscript to state this explicitly after Theorem 5.4 and in the abstract.

Finally we regret any inconvenience caused by the cross-references. Given the strict rebuttal character limit, we used them solely to avoid repetition.

Reviewer 3m6FOpenReview ↗
Rating
4/6
Confidence
2/5
Quality
2/4
Clarity
3/4
Significance
3/4
Originality
3/4
Contribution type
use_inspired
Ethical concerns
NO or VERY MINOR ethics concerns only
Read review
Summary

This paper studies security defense planning for power transmission grids under a three-level defender-attacker-operator decision structure. The authors dualize the inner DC-OPF or SOCP-relaxed AC-OPF problem, merge it with the attacker problem, relax the attack variables, dualize the relaxed problem again, and use Big-M linearization to handle products involving defender variables. This yields an SL-MILP for the DC case and an SL-MICP for the AC/SOCP case. The theoretical part provides a conservative upper bound on the worst-case loss under binary attacks, together with a defense certificate. The experiments compare load shedding and runtime on IEEE/MATPOWER benchmarks in the DC setting, and include an AC case study on the WSCC 9-bus system.

Strengths and weaknesses

The paper targets a meaningful computational bottleneck in tri-level grid defense planning. The sequential structure among defense, attack, and dispatch is natural for this setting, while direct enumeration over attack and defense combinations quickly becomes expensive. The main contribution is to combine OPF dualization, attacker relaxation, a second dualization step, and Big-M linearization into a single optimization problem that can be solved once. Compared with prior tri-level defense models that mainly focus on DC-OPF, the paper also extends the formulation to SOCP-relaxed AC-OPF and provides a conservative certificate. The DC experiments show that, on the selected IEEE cases, the reformulation substantially reduces runtime and produces load-shedding values that are close to exact enumeration or consistent with the stated upper-bound relationship.

My main concerns are as follows.

1.In the final SL-MILP, some auxiliary variables appear in the constraints but are not clearly included in the variable list. Several ρ\rho and σ\sigma terms in the objective also use indices that differ from the derivation. Similar inconsistencies appear in the SL-MICP part, including notation, the dual objective, and multiplier names. These terms define the feasible set and objective of the final problem, so the inconsistencies affect the verifiability of the conservative certificate. The valid bounds for the Big-M constants are not specified.

2.The Big-M constants are central to the reformulation but are not sufficiently specified. The paper does not provide computable bounds for MλM_\lambda, MϕM_\phi, MνM_\nu, MxM_x, or MyM_y, nor does it report the values used in the experiments. Compactness of the original OPF feasible set or Slater feasibility does not by itself give component-wise bounds for the dual variables after merging the attacker and operator problems. This affects both the validity of the certificate and the interpretation of the runtime results.

3.The experiments give useful evidence for the DC case but less for the AC formulation. The paper does not systematically report Strue(dSL∗)S_{\mathrm{true}}(d^*_{SL}) for the selected defenses, so the conservative gap is hard to assess. The AC evaluation is limited to a WSCC 9-bus case and does not include binary-attack recomputation, SOCP tightness checks, Big-M sensitivity, or a comparable baseline. This leaves the practical tightness of the AC certificate unclear.

Questions

1.Can the authors provide corrected full SL-MILP and SL-MICP formulations, with consistent variables, objective terms, auxiliary variables, and constraints?

2.What exact Big-M constants were used in the experiments? How are valid bounds for these constants derived from variable bounds, network parameters, or the relevant dual problems?

3.For the defense solutions in Tables 3 and 4, what are the realized binary-attack values Strue(dSL∗)S_{\mathrm{true}}(d^*_{SL})? Can the authors report the corresponding conservative gap ΔC\Delta_C?

Limitations

The paper discusses conservativeness from the attacker relaxation and the AC relaxation, but does not sufficiently quantify their impact on the certificate. The continuous attacker relaxation may lead to overly conservative defenses, and the SOCP relaxation may differ from the true AC-OPF solution. The choice of Big-M constants and the lack of released code also limit reproducibility and numerical assessment. Since the certificate is central to the reformulation, these boundaries need clearer treatment.

Final justification

Score Unchanged

Thank you for the detailed rebuttal. The authors have addressed most of my original concerns. The notation and formulation issues have been clarified, the Big-MM construction is now described more concretely, and the additional reporting of realized binary-attack values, conservative gaps, and larger AC test cases substantially strengthens the empirical validation. I also appreciate the explicit clarification that the theoretical guarantee for the AC formulation applies to the SOCP-relaxed operator model rather than to the original nonconvex AC-OPF. This appropriately narrows the scope of the certification claim. The remaining limitation is that the theoretical and empirical support for the AC case is still weaker than for the DC case, but I view this primarily as a limitation rather than a fundamental correctness issue. Overall, the rebuttal has substantially strengthened the paper, and I would maintain my current Borderline Accept assessment.

Formatting concerns

No.

1 comment
Authors · RebuttalOpenReview ↗
Rebuttal

W1

We thank the Reviewer for the careful assessment. All identified issues are notational, and none affect the derivations in Appendices B and C (from which the implementation was built) or the proofs in Appendix D; hence, the reported numbers and the certificate logic stand. We will surely fix: (a) the sign slip between eq. (21) and eq. (29b), and correspondingly (22)/(29c); (b) the ρ,σ\rho, \sigma index mismatch between the objective (10) and (SL-MILP) : the multipliers entering the objective are exactly those dual to constraints carrying constant terms M(1−aij)M(1-a_{ij}) and aij≤1a_{ij} \le 1, and the indexing will be made consistent with (38)/(11g); (c) SL-MICP naming the Step-3 multipliers introduced as $\eta_{ij}^{1:4} , \zeta_{ij}^{1:4} , \gamma_{ij}^{0,1} $ (line 198) are the ones appearing as $\rho_{ij}^{1:4} , \sigma_{ij}^{1:4} , \kappa_{ij}^{0,1} $ in Definition 4.4; one naming scheme will be used; (d) every variable which includes the envelopes wij,vijw_{ij}, v_{ij} and yijy_{ij}, will be listed explicitly in the minimization signatures of Definitions 4.2 and 4.4, with a full variable glossary.


W2

We have discussed the setting of big-M bounds in our response to W3 of Reviewer L6eE (Lemma R1, Algorithm 1). Here we answer the main point, which is entirely correct: compactness of the original OPF feasible set (or Slater feasibility of the original problem) does not by itself give component-wise dual bounds after merging the attacker and operator problems. Our argument does not rely on generic compactness. For DC, the bounds are physical and hold for every valid topology zz: the unit shedding penalty caps every nodal price at 1 and every congestion dual at 1 (Lemma R1). For AC, the bound is quantitative Slater applied to the merged relaxed program: the all-shed interior point of Lemma 2.2 (Appendix. D.2) uses no transmission at all (Φ=Ψ=0\Phi = \Psi = 0), so it remains strictly feasible with the identical slack ε^>0\hat\varepsilon > 0 for every z(a,d)z(a,d) with relaxed $a \in [0,1]^m $. The resulting constants Mν=Mϕ=v^/ε^M_\nu = M_\phi = \hat{v}/\hat\varepsilon are computable from network data alone (Algorithm 1, lines 4 to 7), and line 10 of Algorithm 1 provides a per-instance a-posteriori exactness check.


W3

We have reported the Strue(dSL∗)S_{true}(d^*_{SL}) values for the AC-OPF on the 9-bus system in response to Q3 at the bottom. We have further run Sl-MICP on larger MATPOWER systems and summarized the results in response to **Q(i).(c) of Reviewer Qe5o.

We quantified the SOCP relaxation gap on the IEEE 9-bus system by comparing our SOCP formulation with the exact AC-OPF. Both attained the same optimal generation cost ($5296.67) with zero load shedding, while active-power dispatch, voltage magnitudes, and phase angles were nearly identical. This indicates our SOCP relaxation is pretty accurate in approximating the exact AC-OPF.

Generator dispatch (MW/MVar)

Generator Exact pgp_g (MW) Exact qgq_g (MVar) SOCP pgp_g (MW) SOCP qgq_g (MVar)
Gen 1 89.80 12.97 89.80 13.00
Gen 2 134.32 0.03 134.33 5.11
Gen 3 94.19 -22.63 94.18 2.78

Bus voltages and phase angles

Bus Exact ∣vi∣\vert v_i \vert SOCP ∣vi∣\vert v_i \vert Exact $\theta_i $ (rad) SOCP $\theta_i $ (rad)
1 1.100 1.100 0.000 0.000
2 1.097 1.099 0.085 0.084
3 1.087 1.093 0.057 0.059
4 1.094 1.094 -0.043 -0.043
5 1.084 1.084 -0.069 -0.069
6 1.100 1.100 0.011 0.013
7 1.089 1.089 -0.021 -0.018
8 1.100 1.100 0.016 0.014
9 1.072 1.072 -0.081 -0.081

We will include this comparison in the revised manuscript.


Q1

Yes, we have discussed this in response to W1 above.


Q2

The constants and their estimations are discussed in detail in our response to W3 of Reviewer L6eE. For DC, Mλ=Mϕ=1M_\lambda = M_\phi = 1 (valid by Lemma R1: unit shedding penalty + guaranteed slack feasibility of Lemma 2.1) and My=max⁡i,j(θimax⁡−θjmin⁡)M_y = \max_{i,j} (\theta_i^{\max} - \theta_j^{\min} ) from the box bounds in eq. (2a) as in eq. (39); for AC, Mx=max⁡(∣xmin⁡∣,∣xmax⁡∣)M_x = \max(|x^{\min} |, |x^{\max} |) componentwise from eq. (5a) as in eq. (17), and Mν=Mϕ=v^/ε^M_\nu = M_\phi = \hat{v}/\hat\varepsilon from the uniform Slater point of Lemma 2.2. These are derived solely from variable bounds and network parameters; no dual solve is needed.


Q3

We have discussed the optimality gaps for Table 3 (DC) in our responses to W6 and Q of Reviewer L6eE.

For Table 4, we have fixed $d = d_{SL}^* $ and run enumeration on the bilevel problem to obtain the worst case attack (given defense plan $d_{SL}^* $) and the corresponding load shed Strue(DSL∗)S_{true} (D_{SL}^* ). We also do exact enumeration on the tri-level problem to obtain optimal shed S∗S^*, and calculate the exact and conservative gaps Δ0,ΔC\Delta_0, \Delta_C. The results are summarized in the following table:

DD SSLS_{SL} (MW) Strue(dSL∗)S_{true}(d_{SL}^* ) (MW) ΔC\Delta_C (MW) S∗S^* (MW) Δ0\Delta_0 (MW) worst-case attack on $d_{SL}^* $ enumerated tri-level $d^* $
0 125.0 125.00 0.00 125.00 0.00 8–9, 9–4 (none)
1 101.3 100.00 1.30 100.00 0.00 6–7, 7–8 8–9
2 97.3 90.00 7.30 90.00 0.00 4–5, 5–6 6–7, 8–9
3 66.1 12.08 54.02 12.08 0.00 3–6, 8–2 4–5, 6–7, 8–9
4 65.7 12.08 53.62 0.00 12.08 3–6, 8–2 4–5, 3–6, 6–7, 8–9
5 0.0 0.00 0.00 0.00 0.00 (none) 4–5, 3–6, 6–7, 8–9

The result justifies Theorem 5.4 and dSL∗d_{SL}^* as a valid certificate.

Reviewer L6eEOpenReview ↗
Rating
3/6
Confidence
3/5
Quality
2/4
Clarity
2/4
Significance
3/4
Originality
3/4
Contribution type
use_inspired
Ethical concerns
NO or VERY MINOR ethics concerns only
Read review
Summary

This paper reformulates a tri-level Defender-Attacker-Operator problem for power grid security into a single-level MILP/MICP using four-step reformulation pipeline. Both DC-OPF and AC-OPF cases are considered. The theoretical analysis shows the resulting single-level objective gives a conservative upper bound on the true worst-case damage and provides a certificate for the selected defence. Simulations on IEEE benchmark systems comparing with implicit enumeration and Benders/cut-based solvers demonstrate the improvements.

Strengths and weaknesses

Strengths

  1. This paper studies a practical problem defending power grid against line interdiction attacks followed by minimizing damage in the operation.

  2. The reformulation considers both DC and AC OPF.

  3. Some theoretical analysis is provided for a conservative upper bound on the true worst-case damage and a certificate for the selected defence.

Weaknesses

  1. The mathematical reliability: The DC-OPF notation appears inconsistent, for example, the text writes the balance as B(z)x=cB(z)x=c, and the OPF later uses B(z)x=bB(z)x=b.

  2. The certificate seems weaker than the abstract suggests. The key approximation is the relaxation of the attacker's binary variables and the final value is a conservative value under a fractional attacker, not an exact reformulation of the original binary tri-level problem.

  3. The Big-MM treatment is another serious issue, as the exactness depends on valid finite bounds for several dual-variable products. This paper does not provide a convincing way to compute these constants.

  4. Both load shedding and generation cost are considered in the objective but the theoretical discussion often describes the certificate as a bound on worst-case load shedding only. If the objective is a such weighted objective, then the certificate is not automatically a pure load-shedding certificate.

  5. The experiments are quite limited, mostly demonstrated on a small WSCC 9-bus system, which is not sufficient to support the broad claim of practical large-scale grid security.

  6. The other missing piece is that there is no result on quantifying the gaps introduced by the relaxation.

Questions

In addition to the weaknesses, for each reported benchmark, can the authors report Strue(dSL∗)S_{\mathrm{true}}(d^*_{\mathrm{SL}}), the conservative gap ΔC\Delta_C​, and, when exact enumeration is possible, the optimality gap relative to the original binary tri-level problem?

Limitations

Some limitations are discussed at the end, but more should be discussed including larger-scale grid simulations.

Final justification

I raise the quality score to 3 and also the rating to 3, as the responses address several of my earlier concerns in particular regarding the Big-M method.

However, the theoretical support remains much stronger for the DC case than for the AC case. If a comparable AC proof is difficult, stronger experiments could provide useful supporting evidence. Larger benchmarks would be needed to better demonstrate scalability and practical relevance. I consider these remaining issues as limitations.

Formatting concerns

There are some presentation issues, including notation inconsistencies and minor wording errors.

5 comments
Authors · RebuttalOpenReview ↗
Rebuttal

W1

This is a typo. B(z)x=bB(z)x = b in eq. (2b) should be B(z)x=cB(z)x = c.


W2

We believe the results may have been misunderstood. The certificate stated in the abstract is exactly what Theorem 5.4 proves: no feasible binary attack $a \in \mathcal A_{bin} $ can induce damage exceeding the reported value SSLS_{SL}, i.e., P∗(z(a,dSL∗))≤Strue(dSL∗)≤SSL\mathcal P^* (z(a, d_{SL}^* )) \le S_{true}(d_{SL}^* ) \le S_{SL}. We never claim SSL=S∗S_{SL} = S^*; the paper explicitly states that the pipeline is "exact-relax-exact" and that Step 3 is "the only approximation" (Figure 3). We clarify the following three points:

  1. Only one approximation exists, and it is in the safe direction. Steps 1, 2, 4 (in the paper) are exact (Lemmas 2.1, 4.1 for strong duality; Definition A.4 for exact Big-M with binary dijd_{ij}, aija_{ij}). The Step-3 relaxation Abin→Arel\mathcal A_{bin} \to \mathcal A_{rel} only enlarges the attacker's power (proof of Theorem 5.1: Dˉ∗(d)≥D~∗(d)\bar{\mathcal D}^* (d) \ge \tilde{\mathcal D}^*(d)), so it can only inflate the bound, never invalidate it. A "fractional super-attacker" upper-bounds every binary attacker (Remark 5.5). The certificate's validity is unconditional.
  2. The residual conservatism is measurable, not hidden. Remark 5.3 defines ΔC=SSL−Strue(dSL∗)\Delta_C = S_{SL} - S_{true} (d_{SL}^* ) and notes it is computable after solving, by one attacker-operator solve with $d = d_{SL}^* $ fixed (this is the exact merged problem D~∗(dSL∗)\tilde{\mathcal D}^* (d_{SL}^* ) of Step 2, eq. (29a)--(29f), with binary aa, involving no relaxation). This yields the exact realized guarantee Strue(dSL∗)S_{true}(d^*_{SL}) for the deployed defense.
  3. We will sharpen the abstract to state the two-tier structure explicitly: an a-priori conservative bound SSLS_{SL} (Theorem 5.2) plus an exact post-hoc certificate Strue(dSL∗)S_{true}(d^*_{SL}) (Theorem 5.4 + Remark 5.3).

W3

We agree that this is an important point. The valid bounds come from the physics of the load-shedding OPF. In particular, we have the following lemma:

Lemma R1 (physical dual bounds, DC). For every z∈z \in {0,10,1}$^m $, the dual optimal set of (DC-OPF) contains a point with 0≤λi≤10 \le \lambda_i \le 1 and 0≤ϕij−,ϕij+≤10 \le \phi_{ij}^-, \phi_{ij}^+ \le 1. Hence Mλ=1 (≥sup⁡∣Δλij∣M_\lambda = 1 \ (\ge \sup|\Delta\lambda_{ij}|, since both prices lie in [0,1][0,1]) and Mϕ=1 (≥sup⁡∣Δϕij∣)M_\phi = 1 \ (\ge \sup|\Delta\phi_{ij}|) are valid in eqs. (27a)--(27b).

The key physical facts are: (i) the primal is always feasible and bounded for every topology zz, because the shedding slacks si∈[0,ci]s_i \in [0, c_i] allow the operator to shed everything (si=cis_i = c_i, gi=θi=0g_i = \theta_i = 0; proof of Lemma 2.1, Appendix. D.1); (ii) the shedding penalty is 1 per MW (objective es⊤xe_s^\top x); (iii) flow limits are symmetric, −f≤F(z)x≤f-f \le F(z)x \le f (eq. (2c)), so the zero-flow point is strictly interior whenever f>0f > 0.

Proof idea : λi\lambda_i is the sensitivity of PDC∗\mathcal{P}^*_{DC} to the demand cic_i (subgradient of the convex LP value function in its RHS). Upper bound: one extra MW of demand at bus ii can always be served by shedding it (si→si+1s_i \to s_i+1 remains feasible), at cost exactly 1, so λi≤1\lambda_i \le 1. Lower bound: removing demand can never increase the minimal shedding, so λi≥0\lambda_i \ge 0. Flow duals: one extra MW of capacity on line (ij)(ij) can deliver at most one extra MW to some bus, whose marginal value is ≤1\le 1 by the above; hence ϕij±≤1\phi^\pm_{ij} \le 1 (≥0\ge 0 by dual feasibility in eq. (8c)). Adding the boxes λ∈[0,1]n\lambda \in [0,1]^n, ϕ±∈[0,1]m\phi^\pm \in [0,1]^m to the dual (8a)--(8c) is therefore lossless for every zz, and Definition A.4 then makes the Big-M linearization in Step 2 exact with Mλ=Mϕ=1M_\lambda = M_\phi = 1.

The Step-4 constants come from primal boxes and are already exact in the paper, specifically My=max⁡i,j(θimax⁡−θjmin⁡)M_y = \max_{i,j}(\theta_i^{\max} - \theta_j^{\min} ) from eq. (2a), stated in eq. (39); and Mxk=max⁡(∣xkmin⁡∣,∣xkmax⁡∣)M_{x_k} = \max(|x_k^{\min} |, |x_k^{\max} |) from eq. (5a), stated in eq. (59). For the AC case, the bound follows from the quantitative Slater argument using the all-shed point already constructed in the proof of Lemma 2.2 (Appendix. D.2); also, that point uses no lines (Φij=Ψij=0\Phi_{ij} = \Psi_{ij} = 0), so it is strictly feasible with the same slack for every topology zz and every fractional attack aa, which is exactly what a uniform bound requires. Thus, the full procedure becomes:

Algorithm 1: Physically valid Big-M constants (and verification)
Input : demands c (c_i > 0 at load buses), symmetric limits −f ≤ flow ≤ f (f > 0),
        boxes x^min ≤ x ≤ x^max, shedding weight w (DC: w = 1)

# ---- DC (SL-MILP): closed-form, from the physics ----
1: M_λ ← w        # 1 extra MW of demand can always be shed at cost w
                  #   (s_i is a feasibility slack, Lemma 2.1)  ⇒  0 ≤ λ_i ≤ w
2: M_φ ← w        # 1 extra MW of line capacity saves ≤ 1 MW of shed  ⇒  0 ≤ φ±_ij ≤ w
3: M_y ← max_(ij) (θ_i^max − θ_j^min)          # primal box (2a); already eq. (39)

# ---- AC (SL-MICP): uniform Slater bound, from Lemma 2.2's interior point ----
4: x̂ ← all-shed point (Appendix. D.2): g^P = g^Q = u = ε, Φ = Ψ = 0,
        s^P = p^d − ε, s^Q = q^d − ε
5: ε̂ ← minimum constraint slack at x̂
        # strictly positive because p^d_i, q^d_i > 0, f > 0, and Φ = Ψ = 0 lies in
        # ri(K_4) of (5d) and strictly inside the symmetric limits (4a)--(4b);
        # NOTE: x̂ uses no lines ⇒ ε̂ is the SAME for every z and every a ∈ [0,1]^m
6: v̂ ← objective of x̂ = c̃ᵀx̂ + t̂            # ≤ w·Σ_i p^d_i + (small ε-cost)
7: M_ν ← v̂ / ε̂ ;  M_φ ← v̂ / ε̂               # standard Slater bound: any optimal
                                              # dual multiplier ≤ (v̂ − 0)/ε̂,
                                              # since the optimum is ≥ 0
8: M_x ← max(|x^min|, |x^max|) componentwise   # primal box (5a); already eq. (17)

# ---- Verification (both cases; a-posteriori exactness check) ----
9: solve SL-MILP / SL-MICP with the constants above
10: if any envelope constraint (27a)--(27b), (44a)--(44b), (39), or (59) is active
    at its M-bound at the optimum:  M ← 2M, and go to step 9
    # terminates in finite steps as the true duals are bounded (Lemma R1 / step 7)
Output: valid (M_λ, M_φ, M_y) or (M_ν, M_φ, M_x); solution with certified-exact envelopes

Step 10 gives a checkable sufficient condition on the returned solution itself: if no envelope binds, the linearization was exact for that instance, independently of how conservative the analytic constants were. We will definitely clarify this in Appendices A and B of the revised manuscript.


W4

There is no ambiguity for the DC model. The objective is pure load shedding, represented by es⊤xe_s^\top x in the DC-OPF formulation. Therefore, Theorems 5.1 to 5.4 certify load shedding only, which is also what we report in Table 3 and Figure 2.

The weighted objective appears only in the AC model (lines 106–111), where the certificate is for the combined objective (load shedding + generation cost). Pure load-shedding certificates are recovered by simply setting the generation-cost coefficients to zero (see our response to Q(i)(c) of Reviewer Qe5o).


W5

The DC evaluation is not limited to the 9-bus system. Table 3 reports the IEEE 14-bus system, while Figure 2 covers seven benchmark systems (5, 9, 14, 22, 30, 57, and 69 buses), showing 1 to 4 orders-of-magnitude speedups over implicit enumeration and the Benders-cut baseline. Only the AC case study (Table 4) uses the WSCC 9-bus system, so we further run SL-MICP on IEEE 14, 30, and 57 bus systems and summarized the results in response to Q(i).(c) of Reviewer Qe5o.


W6

The paper already defines the two gaps (Remark 5.3):

ΔC=SSL−Strue(dSL∗)\Delta_C = S_{SL} - S_{true}(d_{SL}^* ) and $\Delta_0 = S_{true}(d_{SL}^* ) - S^* $.

Table 3 already reports the total gap $S_{SL}-S^* $ against exact tri-level enumeration. What is missing is its decomposition into ΔC\Delta_C and Δ0\Delta_0. We have now computed and report both quantities. Computing ΔC\Delta_C requires only one additional attacker solve with $d_{SL}^* $ fixed (Step-2, (29a) to (29f)). We similarly report the corresponding relaxation gap for the AC formulation (see our responses to W3 of Reviewer 3m6F and Q(i)(c) of Reviewer Qe5o).


Q

Yes. For each reported benchmark, we will report Strue(dSL∗)S_{\mathrm {true}}(d_{\mathrm{SL}}^* ) and the conservative gap ΔC\Delta_C; whenever exact enumeration of the original binary tri-level problem is tractable, we will additionally report the corresponding optimality gap Δ0\Delta_0.

As discussed in our response to \textbf{W6}, Strue(dSL∗)S_{\mathrm{true}}(d_{\mathrm{SL}}^* ) is obtained by solving the exact merged problem (29a)--(29f) once with the defense $d_{\mathrm{SL}}^* $ fixed, after which ΔC\Delta_C is computed as described in Remark 5.3. For the DC benchmarks, we report Strue(dSL∗)S_{\mathrm{true}}(d_{\mathrm{SL}}^* ), ΔC\Delta_C, and Δ0\Delta_0 in Table 3, since exact tri-level enumeration is tractable for all systems considered.

For AC-OPF, we report Strue(dSL∗)S_{\mathrm{true}}(d_{\mathrm{SL}}^* ), ΔC\Delta_C, and Δ0\Delta_0, separately for load shedding and generation cost, for the IEEE 9-bus system, where exact enumeration is tractable (see our response to Q3 of Reviewer 3m6F). We also provide additional results for larger MATPOWER systems, for which exact enumeration is not tractable, in our response to Q(i)(c) of Reviewer Qe5o.

Reviewer L6eE · CommentOpenReview ↗

Thank the authors for the detailed rebuttal. The rebuttal has clarified several of previous concerns, including the notations in W1, certificate in W2, clarity of load shedding and generation cost in W4, and gap in W6. I'm considering raising the score but would like to follow up on the Big-M in W3 and test cases in W5.

Is a proof under the exact DC-OPF assumptions needed or already provided, as the line-flow dual variables satisfying ϕij±≤w\phi_{ij}^{\pm}\leq w looks intuitive. Does the check that no (M)-bound is active at the returned solution establish global exactness? Authors can choose to clarify or adjust the claim.

The additional 14-, 30-, and 57-bus results improve the evaluation, but these are still considered as small-scale test systems. Usually, some representative larger benchmarks, such as IEEE 118/300 or a PGLib/ACTIVSg cases would be necessary, in particular for the DC case. For example, the ARPA-E Grid Optimization Competition provides test systems with network sizes ranging from 500 to 30,000 buses. A recent benchmark paper PFΔ: A Benchmark Dataset for Power Flow under Load, Generation, and Topology Variations in NeurIPS 2025 considered IEEE-14, IEEE-30, IEEE-57, IEEE118, GOC-500, and GOC-2000. Given the limited time, authors can consider this as a limitation.

Authors · CommentOpenReview ↗

We sincerely thank the reviewer for the positive follow-up and are encouraged that the rebuttal has addressed the major concerns regarding notation, certification, objective formulation, and relaxation gaps.


Regarding W3 (Big-MM): Yes. Under the DC-OPF assumptions, the required bounds are already established in Lemma R1 from the physics of the load-shedding OPF, while Algorithm 1 provides a constructive procedure for computing every Big-MM constant. The final a-posteriori verification is a sufficient certificate of exactness of the Big-MM reformulation: if none of the Big-MM envelopes is active at the optimum, then the linearized MILP coincides with the original complementarity-constrained formulation for that instance, i.e., no artificial constraint affects the returned optimum. This verification is independent of how conservative the analytic bounds are. We will explicitly clarify this point in the revised manuscript.


Regarding W5 (larger-scale systems): We thank the reviewer for this valuable suggestion. Following the reviewer's recommendation, we have run the tri-level DC-OPF on the IEEE 118-bus system with settings similar to those in Table 4 of the paper (and the table in response to Q3 of the Reviewer 3m6F). The proposed SL-MILP continues to produce conservative certificates, with all reported instances satisfying ΔC≥0\Delta_C \ge 0 and Δ0≥0\Delta_0 \ge 0 (and close to zero).

DD SSLS_{SL} Strue(dSL∗)S_{true}(d_{SL}^* ) ΔC\Delta_C S∗S^* Δ0\Delta_0
0 110.0 110.0 0.0 110.0 0.0
1 105.2 104.8 0.4 104.0 0.8
2 51.6 49.3 2.3 48.1 1.2
3 45.0 43.6 1.4 42.1 1.5
4 44.8 43.1 1.7 42.0 1.1
5 43.8 42.3 1.5 41.0 1.3

We agree that even larger, industry-oriented benchmark suites such as ARPA-E and PFΔ would provide an important next step. Unlike the classical IEEE test cases, these datasets incorporate significantly richer operational complexity (e.g., security-constrained AC-OPF, multiple operating scenarios and contingencies, and additional discrete controls), resulting in substantially larger mixed-integer optimization problems. Extending our compact single-level reformulation to these realistic benchmark suites is therefore a natural and important direction for future work, and we will explicitly acknowledge this as one of the limitations of the current work in the revised manuscript.